Condenser Water LoopSystem

General Overview

A condenser water (CW) loop consists of a CW pump and motor, an evaporative cooling tower with a fan and motor, and a CW piping network. The CW loop system is designed to reject the heat given off by the condenser side of the chiller. A CW loop can have the following configurations:

Variable-speed Fans and Constant-flow System

A variable-speed constant-flow CW loop consists of variable-speed cooling tower fans and constant-speed CW pumps.

Variable-speed Fans and Variable-flow System

A variable-speed variable-flow CW loop consists of variable-speed CW pumps and a cooling tower with variable-speed fans.

Constant-speed Fans and Constant-flow System

A constant-speed constant-flow CW loop consists of constant-speed cooling tower fans and constant-speed CW pumps.

Components

The main components associated with the condenser water loop are shown in Figure 1.

Figure 1. Condenser water loop components.
Figure 1. Condenser water loop components (click on image to enlarge).

Condenser Water Pump and Motor

A condenser water pump and motor circulates condenser water from the condenser section of the chiller to the cooling tower. A condenser water loop pump and motor can be constant speed or equipped with variable frequency drives (VFDs).

tip
Taylor (2012) provides scenarios that limit the cost effectiveness of VFDs on condenser loop pumps.

Constant-speed, Constant-volume Pump

A constant-speed condenser water pump provides a fixed flow to the cooling tower and chiller, independent of cooling tower heat rejection capacity or building cooling load. Learn More

Variable-speed, Variable-volume Pump

A variable-speed condenser water pump and motor modulates the flow to the cooling tower and chiller based on the heat rejection capacity of the cooling tower and the minimum flow rate required through the condenser section of the chiller. Learn More

Evaporative Cooling Tower

An evaporative cooling tower rejects heat from the condenser section of the chiller, using forced airflow and the latent heat of evaporation to provide the cooling effect on the condenser water. A cooling tower may have one or more sections (called cells). Each cell typically has one fan and motor. The cooling tower fan and motor may operate at a constant or variable speed.

Constant-speed, Constant-volume Cooling Tower Fan

The overall cooling capacity of the condenser water loop in a cooling tower with multiple cells and constant speed fans and motors is controlled by staging (turning on) the cells. Learn More

Variable-speed, Variable-volume Cooling Tower Fan

Cooling towers with variable speed fans and motors generally operate the fans at the lowest speed possible and stage fans based on the overall CW heat rejection needed to satisfy the specific sequence of operation of the chilled water plant. Learn More

Figure 2. Evaporative Cooling Tower.
Figure 2. Evaporative Cooling Tower (click on image to enlarge).

Evaluation of Energy Consumption

The primary energy consumption of a condenser water loop is the electricity used for the pump motors and the cooling tower fans. Table 1 provides a summary of system component measurements and value calculations needed to quantify the annual energy consumption and operating characteristics of a CW loop.

Table 1. Key values, components and measurements to evaluate energy consumption.
System Quantification Value to be Quantified Energy Consuming Components Measurements
Variable-flow CW loop electricity usage (kWh)
  • Average hourly pump motor kWh
  • Total operating time for the pump
Variable-speed pump motor
Variable-speed cooling tower electricity usage (kWh)
  • Average hourly fan motor kWh
  • Total operating time for the fan
Variable-speed cooling tower fan motors
Constant-flow CW loop electricity usage (kWh)
  • Average hourly pump motor kWh
  • Total operating time for the pump
Constant-speed pump motor
Constant-speed cooling tower electricity usage (kWh)
  • Average hourly fan motor kWh
  • Total operating time for the fan
Constant-speed cooling tower fan motors
Heat rejected to the outdoors Average hourly Btu rejected from the condenser water loop

Measurement Locations

The measurements for the condenser water loop are schematically shown in Figure 3, include:

Figure 3. Condenser water loop measurement locations.
Figure 3. Condenser water loop measurement locations (click on image to enlarge).

Further Reading

  • ASHRAE (2020). “ASHRAE Handbook: HVAC Systems and Equipment,” Chapter 40. COOLING TOWERS. I-P Edition.

  • Taylor, S (2012). “Optimizing Design & Control of Chilled Water Plants Part 5: Optimized Control Sequences”. ASHRAE Journal, Vol. 54, No 6. American Society of Heating, Refrigerating and Air Conditioning Engineers; pp: 56-74.