Water-cooled Chilled Water PlantPlant

General Overview

A water-cooled chilled water plant consists of a water-cooled chiller system, a condenser water loop system and a chilled water loop system operating to meet cooling demand in a facility. If a waterside economizer is implemented in the facility, the chilled water plant includes a waterside economizer system as well.

Figure 1. Water-cooled chilled water plant.
Figure 1. Water-cooled chilled water plant (click on image to enlarge).

Water-cooled Chilled Water Plant Systems and Components

Water-cooled Chiller System

A water-cooled chiller produces chilled water through the basic refrigeration cycle to the chilled water loop to distribute to the facility. The primary systems and components of a water-cooled chiller are shown in Figure 2.

Figure 2. Water-cooled chiller.
Figure 2. Water-cooled chiller (click on image to enlarge).

Chilled Water Loop System

A chilled water loop consists of a closed loop distribution system that supplies chilled water to the building. Components of a chilled water loop are shown in Figure 3.

Figure 3. Chilled water loop.
Figure 3. Chilled water loop (click on image to enlarge).

Condenser Water Loop System

A condenser water loop consists of an open loop distribution system that circulates condenser water from a chiller condenser to a cooling tower where the condenser water is cooled and returned to the chiller condenser. Components of a condenser water loop are shown in Figure 4.

Figure 4. Condenser water loop.
Figure 4. Condenser water loop (click on image to enlarge).

Waterside Economizer System

Waterside economizers may use an external plate-and-frame heat exchanger between the condenser and chilled water loop or the chiller itself may be set up to perform the function of a waterside heat exchanger. When the outdoor temperatures are favorable, heat from the chilled water loop may be rejected directly to the condenser water loop through a heat exchanger without running the chiller compressor motor. Components of a waterside economizer system are shown in Figure 5.

Figure 5. Waterside economizer system.
Figure 5. Waterside economizer system (click on image to enlarge).

Evaluation of Energy Consumption

The primary energy consumption of a water-cooled chilled water plant is the sum of the energy consumption of the components of each system. The thermal energy rejected from the building to the outdoors can also be measured to evaluate the overall performance of the plant, usually in kilowatts of power consumed per ton of cooling provided (kW/ton). Table 1 provides a summary of system component measurements and values needed to quantify the annual energy consumption and operating characteristics of the water-cooled chilled water plant.

Table 1. Key values and components to measure to evaluate energy consumption.

Plant Quantification

Values to be Quantified

Energy Consuming Component

Water-cooled chilled water plant electricity usage (kWh)

  • Average hourly chiller (kWh)
  • Average hourly pump motors (kWh)
  • Average hourly cooling tower fan motors (kWh)
  • Chiller compressor motor
  • Chilled water pump motors
  • Condenser water pump motors
  • Heat exchanger pump motor (if present)
  • Cooling tower fan motors

Cooling load on building/Heat rejected to the outdoors

Average hourly thermal load on chiller evaporator (Btu/h)

Coefficient of Performance (COP)

  • Electricity input
  • Cooling load output

Further Reading

  • ASHRAE (2019). “ASHRAE Handbook: HVAC Applications,” Chapter 43. SUPERVISORY CONTROL STRATEGIES AND OPTIMIZATION. I-P Edition.

  • ASHRAE (2019). “ASHRAE Handbook: HVAC Applications,” Chapter 48. DESIGN AND APPLICATION OF CONTROLS. I-P Edition.

  • ASHRAE (2020). “ASHRAE Handbook: HVAC Systems and Equipment,” Chapter 38. COMPRESSORS. I-P Edition.

  • ASHRAE (2020). “ASHRAE Handbook: HVAC Systems and Equipment,” Chapter 40. COOLING TOWERS. I-P Edition.

  • Consulting Specifying Engineer (2021). “Understanding chilled water plant performance”. Consulting - Specifying Engineer | Understanding chilled water plant performance (csemag.com).

  • Taylor, S (2012). “Optimizing Design & Control of Chilled Water Plants Part 5: Optimized Control Sequences”. ASHRAE Journal, Vol. 54, No 6. American Society of Heating, Refrigerating and Air Conditioning Engineers; pp: 56-74.

  • Taylor, S (2014). “How to Design & Control Waterside Economizers.” ASHRAE Journal, Vol. 56, No 6. American Society of Heating, Refrigerating and Air Conditioning Engineers; pp: 30-36.