Waterside EconomizerSystem

General Overview

A waterside economizer is used to cool or partially cool the chilled water without mechanical heat transfer when outdoor air temperatures are cold enough to meet the building’s cooling demand. Typical waterside economizer systems have an external heat exchanger, however sometimes the chiller itself may be set up to perform the function of a waterside heat exchanger.

Waterside Economizer Components

The components associated with a waterside economizer are heat exchanger, piping, and valves. These components are shown in Figure 1.

Figure 1. Waterside economizer system components.
Figure 1. Waterside economizer system components (click on image to enlarge).

External Heat Exchanger

Typical heat exchangers installed in waterside economizers systems are plate and frame heat exchangers. They can be configured as integrated and non-integrated economizers. The non-integrated configuration consists of a plate-and-frame heat exchanger (PFHX) in parallel with chillers and requires the heat exchanger to supply the entire cooling load. An integrated configuration, the PFHX are arranged in series allowing the chiller to utilize pre-cooled chilled water and minimizing the energy required by chillers.

Piping, fittings, and valves

Piping can have different arrangements to allow the desirable operation of the waterside economizer.

Evaluation of Energy Consumption

The primary effect of waterside economizer is the savings in electricity usage at plant level to meet the cooling load of the building. For more information about the energy consumption of the overall water-cooled chilled water plant see the Water-Cooled Chilled Water Plant.

The cooling energy savings are equivalent to the heat rejected through the waterside economizer. Table 1 provides a summary of the components to measure to arrive at values needed to quantify the heat rejected from the chilled water to condenser water by free cooling.

Table 1. Key values and measurements to evaluate heat transfer.

System Quantification

Values to be Quantified

Energy Consuming Components

Measurements

Waterside economizer heat rejection load

Hourly Btu/h transferred, differential of temperature for chilled water loop.

Heat exchanger of waterside economizer

Measurement Locations

The measurement locations for the waterside economizer are schematically shown in Figure 2:

Figure 2. Waterside economizer measurement locations.
Figure 2. Waterside economizer measurement locations (click on image to enlarge).

Further Reading