Water-cooled ChillerSystem

General Overview

The water-cooled chiller system produces chilled water through the basic refrigeration cycle and consists of an evaporator, a compressor, a condenser, and an expansion valve. The system can be constant-speed or variable-speed.

Constant-speed System

A constant-speed water-cooled chiller has a compressor motor that runs at a constant speed based on the total capacity of the chiller and adjusts the refrigerant flow with modulating vanes in the compressor when partial capacity of the chiller is needed.

Variable-speed System

A variable-speed water-cooled chiller has a variable frequency drive on the compressor motor and can reduce the speed of the compressor during partial load conditions.

Water-cooled Chiller Components

The four main components of every chiller are an evaporator, a compressor and motor, a condenser, and an expansion valve. The components are shown in Figure 1.

Figure 1. Water-cooled chiller components.
Figure 1. Water-cooled chiller components.

Evaporator

The evaporator transfers heat from the chilled water loop to the refrigerant through a heat exchanger.

Compressor

The compressor increases the temperature and pressure of the refrigerant between the evaporator and condenser sections of a chiller. A chiller may have one or more compressors. Water-cooled chillers typically have centrifugal compressors. Centrifugal compressors are dynamic compressors which increase refrigerant vapor pressure by converting the velocity pressure from the rotating impellers to static pressure in the discharged vapor. They can be driven with a constant-speed motor or a motor with a variable frequency drive (VFD). A centrifugal compressor with a constant-speed motor uses variable guide vanes to change the speed of the gas as it enters the compressor, which changes the centrifugal force and the lift. Lift in a chiller system refers to the difference between the condenser water temperature leaving the chiller and the chilled water temperature leaving the chiller. A centrifugal compressor with a VFD on the motor varies the speed of the impeller to control the lift.

Condenser

The condenser rejects heat from the refrigerant to the condenser water loop through a heat exchanger.

Expansion Valve

The expansion valve depressurizes the warm refrigerant between the condenser and evaporator to reduce the temperature of the refrigerant, then the cold refrigerant is delivered to the evaporator to pick up more heat from the chilled water loop.

Evaluation of Energy Consumption

The primary energy consumption in a water-cooled chiller is the electricity used by the compressor motor and its controls. Thermal energy rejected by the chiller to the outdoors can be measured to evaluate the overall performance of the chiller, which can be expressed as kilowatts of power consumption per ton of cooling provided (kW/ton). Table 1 provides a summary of system component measurements and values needed to quantify the annual energy consumption and operating characteristics of a water-cooled chiller.

Table 1. Key values, components and measurements

System Quantification

Values to be Quantified

Component to be Measured

Measurements

Constant-speed water-cooled chiller power draw

Average hourly chiller kWh and annual operating time for the chiller

Constant-speed compressor motor and controls

Variable-speed water-cooled chiller power draw

Hourly chiller kWh and annual operating time for the chiller

Variable-speed compressor motor and its controls

Cooling load on building/Heat rejected to the outdoors

Hourly chilled water temperature difference across evaporator (F)

Evaporator

Hourly temperature of chilled water entering and leaving the chiller evaporator

Hourly condenser water temperature difference across condenser (F)

Condenser

Hourly temperature of chilled water entering and leaving the chiller condenser.

Hourly chilled water flow rate (GPM)

Chilled water pump

Hourly measurement of chilled water flow rate

Hourly condenser water flow rate (GPM)

Condenser water pump

Hourly measurement of condenser water flow rate

Measurement Locations

The measurement locations for a water-cooled chiller are schematically shown in Figure 2.

Figure 2. Water-cooled chiller measurement points.
Figure 2. Water-cooled chiller measurement points.

Further Reading

  • ASHRAE (2020). “ASHRAE Handbook: HVAC Systems and Equipment,” Chapter 38. COMPRESSORS. I-P Edition.

  • Consulting Specifying Engineer (2021). “Understanding chilled water plant performance”. Consulting - Specifying Engineer | Understanding chilled water plant performance (csemag.com).