Air-cooled Chilled Water PlantPlant

General Overview

An air-cooled chilled water plant consists of an air-cooled chiller system and a chilled water loop system operating to meet the cooling demand in a facility. The air-cooled chiller produces chilled water through the basic refrigeration cycle. The primary chilled water pump circulates the chilled water between the chiller and the chilled water loop. In some cases, a secondary chilled water pump distributes the chilled water produced by the chiller to air handling units (AHUs) in the building.

Figure 1. Air-cooled chilled water plant.
Figure 1. Air-cooled chilled water plant (click on image to enlarge).

Air-cooled Chilled Water Plant Systems and Components

Air-cooled Chiller System

Figure 2 shows an air-cooled chiller providing chilled water to the chilled water loop system and components.

Figure 2. Air cooled chiller.
Figure 2. Air-cooled chiller (click on image to enlarge).

Chilled Water Loop System

A chilled water loop system consists of a closed loop distribution system that supplies chilled water to the building and includes components (see Figure 3).

Figure 3. Chilled water loop.
Figure 3. Chilled water loop (click on image to enlarge).

Evaluation of Energy Consumption

The primary energy consumption of an air-cooled chilled water plant is the sum of the energy consumption of the components of each system. The thermal energy rejected from the building to the outdoors can also be measured to evaluate the overall performance of the plant, usually in kilowatts of power consumer per ton of cooling provided (kW/ton). Table 1 provides a summary of system component measurements and values needed to quantify the annual energy consumption and operating characteristics of an air-cooled chilled water plant.

Table 1. Key values and components to measure to evaluate energy consumption.

Plant Quantification

Values to be Quantified

Energy Consuming Component

Air-cooled chilled water plant electricity usage (kWh)

  • Condenser fan motor
  • Compressor motor
  • Chilled water pump motors

Cooling load on building/Heat rejected to the outdoors

Average hourly thermal load of chiller evaporator (Btu/h)

Further Reading

  • ASHRAE (2020). 2020 ASHRAE Handbook: HVAC Systems and Equipment. Atlanta, GA: ASHRAE.

  • Gordon, J.M.; Ng, K.C. (2000). Cool thermodynamics: The engineering and physics of predictive, diagnostic and optimization methods for cooling systems. Cambridge International Science Publishing; pp. 159-177.

  • Wei, J.; Reddy, T.A. (2003). “Reevaluation of the Gordon-Ng Performance Models for Water-Cooled Chillers.” ASHRAE Transactions, Vol. 109, Part 2. Atlanta, GA: American Society of Heating, Refrigerating and Air Conditioning Engineers.